Serious
Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard
The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep.
The hazard
On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.
Injuries and incidents
None reported.
The remedy
All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.
Recall details
Have this product?
Follow the remedy in the official notice. CPSC lists the exact models and where it was sold.
Open CPSC noticeCompany pages: Bosch Security Systems
Source: CPSC. Defect Index is independent and not affiliated with CPSC.