Home/Products/Recall 13720

Serious

Siemens Recalls Temperature and Humidity Sensors for Schools, Hospitals and Other Buildings Due to Fire Hazard

This recall involves wall-mounted Q-series sensors that control heat, air conditioning and humidity inside commercial buildings, hospitals and schools.

The hazard

The sensors can overheat, posing a fire hazard.

Injuries and incidents

Four incidents of overheating and fires have been reported to Siemens. Two of the fires were in schools and two in hospitals. Minor damage was reported. No injuries have been reported.

The remedy

Consumers should look to see if their sensors are currently operating on an AC power source and, if they are, consumers should immediately have the recalled sensors converted to a DC power source. Consumers should contact Siemens to schedule the installation of a free replacement sensor. Siemens is directly contacting owners of the recalled sensors.

Recall details

Recall number13720
DateJan 22, 2013
CompanySiemens
Product typeThermostats/Thermometers/Sensors
Units affected57,000

View the official CPSC notice

Have this product?

Follow the remedy in the official notice. CPSC lists the exact models and where it was sold.

Open CPSC notice

Company pages: Siemens

Source: CPSC. Defect Index is independent and not affiliated with CPSC.